Maintenance Activity

Maintenance Schedule — Text Version

Monthly Inspection — check, record, correct

Flooded Systems

  • System float voltage
  • Battery, rack and area cleanliness
  • Charger output current and voltage
  • Electrolyte levels
  • Cracks in cells or evidence of leakage
  • Corrosion at posts, connections, and racks
  • Ambient temperature and ventilation
  • Pilot-cells voltage and electrolyte temperature
  • Pilot-cells specific gravities
  • Ground connection and faults
  • Monitoring system operation (if installed)
  • Spill containment system integrity

VRLA Systems

  • System float voltage
  • Battery Rack/Cabinet cleanliness
  • Charger output current and voltage
  • Cracks in cells or evidence of leakage
  • Corrosion at posts, connections, and racks
  • Ambient temperature and ventilation
  • DC current per string
  • Ground connection and faults
  • Monitoring system operation (if installed)
  • Spill containment system integrity

Quarterly/Semi-Annual — check, record, correct

Flooded Systems

  • All of the monthly checks
  • Voltage of each block or cell if possible
  • Specific gravities of 10% of the cells of the string.
  • Electrolyte temperature of 10% of the cells.
  • Torque and or DLRO of 10% of the cells.

VRLA Systems

  • All of the above checks
  • Voltage of each block or cell if possible
  • Internal ohmic reading of all cells/blocks
  • Temperature of each cell

Annual Maintenance — check, record, correct

Flooded Systems

  • All of the monthly checks
  • Voltage of each block or cell
  • Specific gravities and temperatures of all cells
  • Cell condition.
  • Cell to cell connection resistances.
  • Structural integrity of battery rack.

VRLA Systems

  • All of the above checks
  • Cell to cell connection resistances.
  • AC Ripple current
  • Structural integrity of battery rack/cabinet