Maintenance Schedule — Text Version
Monthly Inspection — check, record, correct
Flooded Systems
- System float voltage
- Battery, rack and area cleanliness
- Charger output current and voltage
- Electrolyte levels
- Cracks in cells or evidence of leakage
- Corrosion at posts, connections, and racks
- Ambient temperature and ventilation
- Pilot-cells voltage and electrolyte temperature
- Pilot-cells specific gravities
- Ground connection and faults
- Monitoring system operation (if installed)
- Spill containment system integrity
VRLA Systems
- System float voltage
- Battery Rack/Cabinet cleanliness
- Charger output current and voltage
- Cracks in cells or evidence of leakage
- Corrosion at posts, connections, and racks
- Ambient temperature and ventilation
- DC current per string
- Ground connection and faults
- Monitoring system operation (if installed)
- Spill containment system integrity
Quarterly/Semi-Annual — check, record, correct
Flooded Systems
- All of the monthly checks
- Voltage of each block or cell if possible
- Specific gravities of 10% of the cells of the string.
- Electrolyte temperature of 10% of the cells.
- Torque and or DLRO of 10% of the cells.
VRLA Systems
- All of the above checks
- Voltage of each block or cell if possible
- Internal ohmic reading of all cells/blocks
- Temperature of each cell
Annual Maintenance — check, record, correct
Flooded Systems
- All of the monthly checks
- Voltage of each block or cell
- Specific gravities and temperatures of all cells
- Cell condition.
- Cell to cell connection resistances.
- Structural integrity of battery rack.
VRLA Systems
- All of the above checks
- Cell to cell connection resistances.
- AC Ripple current
- Structural integrity of battery rack/cabinet